Megatro 1000kv-10A2-Zbc5 Sc Suspension Transmission Structure

  • Model NO.: MGP-1000KV--10A2-ZBC5
  • Conductor Circuit: Single Circuit
  • Materials: Steel
  • Style: Independence Tower
  • Design Software: Pls
  • Accessories 2: Conductor and Cable
  • Accessories 4: Tower Earthing Kits
  • Transport Package: Export Standard Package
  • Origin: Shandong, China
  • Usage: Crossing Tower, Tension Tower, Angle Tower, Terminal Tower, According to Client Requirements
  • Certification: ISO
  • Standard: Nonstandard
  • Structure: According to Client Requirements
  • Accessories 1: Powerfitting
  • Accessories 3: Tower Foundtion
  • Trademark: MEGATRO
  • Specification: As per client requirements
  • HS Code: 73082000
MEGATRO 1000KV-10A2-ZBC5 SC tangent transmission tower
This photo refers to our 1000KV-10A2-ZBC5 SC tangent transmission tower, it is widely used in our Chinese market. Some of technical features of this tower as follow:
1 climate condition
Item Temperature (ºC) Wind speed (m/s) Ice thickness (mm)
Max. temperature 40 0 0
Mini. temperature -20 0 0
Ice thickness -5 10 10
Basic wind speed -5 27 0
Installation condition -10 10 0
Annual temperature 15 0 0
Lightning overvoltage 15 10 0
Operation overvoltage 15 16 0
2 Technical specification of conductor and OPGW

Item
Conductor OPGW
JL/G1A-500/35 JLB20A-170

construction
AL 45×3.76  
Steel(Al wrap steel ) 7×2.51 19×3.4

Cross-section
(mm2)
Al 500.00 43.13
Steel 34.60 129.37
Total 535.00 172.5
Diameter 30.11 17.01
Length mass (kg/km) 1650.2 1152.0
Elastic module (MPa) 63000 147200
coefficient of linear expansion (1/ºC) 20.9×10-6 13.0×10-6
Rated broken (N) 119410 203380
3 tower design data
Tower
type
Nominal
Height
Scope (mm)
Horizontal
span
(m)
Vertical
Span
(m)
Angle
º
Nominal height tower weight Kg
1000KV-10A2-ZBC5 42 550 800 0~20 93551
4 type and force of conductor and OPGW

Power
voltage

1000KV-10A2-ZBC5
Conductor
type
8×JL/
GIA-500/35
Max. operation
Tension force
(KN/phase)

363.006

Un-balance
Stress value(%)

0
OPGW
Type
JLB20A-170 Max. operation
Tension force
(KN/pc)
56.827

 
Un-balance
Stress value(%)

0
 
5 Operation data

Item
 
Horizontal
span
(m)
Vertical
Span
(m)
Representative
Span (m)
Angle
º
Height
(m)

KV
 
data 1000 1550 400 0 660 0.5
6 loading data

Site condition
Normal operation condition Accident condition Installation
condition
Non-uniform
Ice condition
Basic wind speed Ice Mini.
temperature
Non-
broken
broken
Climate condition
(t/v/b)
-5/30/0 -5/10/10 -30/0/0 -5/0/10 -5/0/10 -15/10/0 -5/10/10
Horizontal loading conductor 174082 29400 -- --- --- 16170 0
Insulator
Power fitting
37002 288 --- --- ---- 288 0
Jump & string              
OPGW 15866 3445 --- --- --- 1473 0
Vertical loading


 
conductor 205735 343170 205735 205735 205735 339464 274452
Insulator
Power fitting
23000 25256 23000 23000 23000 LiFePO4 For Solar/Wind Energy System